Skip to content

Dimens® a registered trademark of RST Elektronik · Since 2008

Magmeter: How Magnetic Flow Meters Work

A magmeter, short for magnetic flow meter or electromagnetic flow meter, measures the volumetric flow of an electrically conductive liquid without placing anything in the flow path. Coils around the pipe generate a magnetic field, the moving liquid acts as a conductor passing through that field, and a voltage appears across two electrodes in the pipe wall. That voltage is directly proportional to flow velocity.

Because there is no obstruction, no moving part and no pressure drop, a magmeter handles slurries, chemicals, wastewater and pulps that would destroy a mechanical meter. It also carries one hard limitation that rules it out entirely for a large class of fluids. This guide covers the working principle, that limitation, the accuracy you can realistically expect, and how to size and install a magmeter correctly.

What Is a Magmeter?

A magmeter is a volumetric flow meter with no moving parts. The measuring section is a straight length of pipe with an insulating liner, a pair of field coils outside it and two electrodes in contact with the liquid. Nothing protrudes into the bore, so the meter presents the same flow resistance as an equivalent length of pipe.

The terms magmeter, magnetic flow meter, electromagnetic flow meter and mag flow meter all describe the same instrument. Electromagnetic flow meter is the term used in most European specification documents; magmeter is the shorter form common in water, wastewater and North American practice.

How a Magmeter Works: Faraday’s Law in Practice

The measurement rests on Faraday’s law of electromagnetic induction: a conductor moving through a magnetic field generates a voltage proportional to its velocity. In a magmeter the conductor is the process liquid itself.

  1. Field coils on opposite sides of the measuring tube are energised, producing a magnetic field across the bore, perpendicular to the direction of flow.
  2. The conductive liquid flows through that field. Charge carriers in the liquid are deflected towards the pipe wall, and a potential difference develops across the bore at right angles to both the field and the flow.
  3. Two electrodes mounted flush in the liner, on the axis perpendicular to the field, pick up that voltage. The signal is typically in the microvolt to millivolt region.
  4. The transmitter amplifies the signal and calculates velocity. Multiplying velocity by the known cross-sectional area of the tube gives volumetric flow.

The output is linear with velocity, which is a significant practical advantage over differential pressure flow measurement, where flow varies with the square root of the measured quantity and rangeability suffers as a result.

Almost all modern magmeters use a pulsed direct-current field rather than a continuous alternating field. The coils are switched, and the transmitter samples the electrode voltage during both the energised and the de-energised phase. Subtracting the two removes electrochemical offset at the electrodes and stray plant noise, which is what allows a magmeter to hold its zero over years without recalibration.

The Conductivity Requirement

A magmeter can only measure a liquid that conducts electricity. This is the one specification that decides whether the technology is viable at all, and it should be checked before anything else.

Most instruments require a minimum conductivity of about 5 microsiemens per centimetre, with some designs working down to 1 µS/cm. For reference, ordinary tap water sits between roughly 50 and 800 µS/cm and industrial wastewater is usually higher, so both are comfortably measurable.

FluidTypical conductivityMagmeter suitable
Potable and process water50 to 800 µS/cmYes
Municipal and industrial wastewaterAbove 1,000 µS/cmYes
Acids, caustics and brinesVery highYes, subject to liner and electrode choice
Slurries, pulp stock, mining tailingsVariable, usually highYes, a primary application
Demineralised and ultrapure waterBelow 1 µS/cmNo
Hydrocarbons, oils, fuels, solventsEffectively zeroNo
Gases and steamNot applicableNo

For non-conductive liquids, hydrocarbons above all, the alternatives are a Coriolis mass flow meter, a turbine flow meter, a positive displacement meter for viscous service, or an ultrasonic flow meter.

Magmeter Accuracy and Turndown

Typical magmeter accuracy is ±0.2 to ±0.5 percent of reading over the usable velocity range, with the better figures requiring individual wet calibration. Note the basis: percentage of reading, not of full scale. Unlike a device rated as a percentage of span, a magmeter’s absolute error falls as flow falls, which is why it holds useful accuracy across a wide turndown.

Usable turndown is commonly 20 to 1 or better, limited at the low end not by the electronics but by velocity. Below roughly 0.3 m/s the induced voltage becomes small relative to noise, and below roughly 0.15 m/s solids may settle in the bore. The practical design window is 1 to 5 m/s.

VelocityBehaviourRecommendation
Below 0.3 m/sSignal approaches the noise floor; accuracy degradesReduce the meter bore below line size
0.3 to 1 m/sUsable but at reduced accuracyAcceptable for totalising, marginal for control
1 to 5 m/sOptimum measurement windowSize for this band
5 to 10 m/sAccurate but liner and electrode wear acceleratesAcceptable for clean liquids only
Above 10 m/sAbrasive wear and cavitation riskIncrease the meter bore

Liner Materials

The liner electrically isolates the measuring signal from the metal pipe body and is the component that faces the process chemistry and any abrasion. It is the most consequential selection decision after the meter size.

LinerTemperature limitStrengthsAvoid where
PTFEAround 130 °CBroadest chemical resistance, non-stick, suits acids and causticsAbrasive slurries; vacuum service without support
PFAAround 150 °CSimilar chemistry to PTFE with better mechanical strength and vacuum capabilityHeavy abrasion
Hard rubberAround 80 °CLow cost, good for water and wastewaterAggressive chemicals, higher temperatures
PolyurethaneAround 80 °CExcellent abrasion resistance for slurries and mining dutyAcids, solvents, elevated temperature
CeramicAbove 150 °CHighest abrasion and temperature capability, very low driftThermal shock; applications sensitive to fragility

Electrode Materials

Electrodes must remain in electrical contact with the liquid and resist corrosion and coating. Stainless steel 316L covers the majority of water and general industrial duty. Hastelloy C is specified for chlorides, seawater and most acids. Titanium and tantalum are reserved for aggressive acid and brine service. Platinum is used where nothing else survives.

Where the process deposits an insulating film, greasy wastewater and some pulp stocks in particular, a bullet-nose or protruding electrode geometry helps the flow scour the surface. Where deposits are unavoidable, a capacitive electrode design measures through the liner without direct wetted contact, at additional cost.

Sizing a Magmeter

Magmeters are sized on velocity, not on line size. Fitting a meter of the same nominal diameter as the pipe is the most common sizing error and produces poor performance whenever the pipe is generously sized for pressure loss.

  1. Establish minimum, normal and maximum flow rates, not just the design maximum.
  2. Calculate the velocity each of those produces in the candidate bore.
  3. Aim to place the normal flow between 1 and 3 m/s.
  4. If the minimum flow falls below 0.3 m/s, select a smaller meter bore and fit reducers. A reduced-bore meter with concentric reducers is standard practice and is preferable to a correctly sized pipe with an undersized signal.

Installation Requirements

  • Full pipe. The bore must remain full at all times. A partially filled pipe gives a reading that is wrong rather than merely noisy. Install in a rising line, or at the low point of the system, and never at a high point where air can collect.
  • Straight run. Allow five pipe diameters upstream and two or three downstream as a working minimum. More is needed downstream of a pump, a partially open valve or two elbows in different planes.
  • Electrode orientation. Mount the meter so that the electrode axis is horizontal. This keeps both electrodes away from any air at the crown of the pipe and any sediment at the invert.
  • Earthing. The liquid must be referenced to the transmitter earth. Use earthing rings or earthing electrodes with plastic and lined pipework. Poor earthing is the single most common cause of an unstable magmeter reading.
  • Vibration and strain. Support the adjacent pipework so that no pipe strain is carried through the meter body.

Where Magmeters Beat the Alternatives

Compared withMagmeter advantageMagmeter disadvantage
Differential pressure and orifice plateNo permanent pressure loss; linear output; far wider turndownHigher capital cost; conductive liquids only
Turbine flow meterNo moving parts; tolerates solids and abrasion; no bearing wearCannot measure hydrocarbons or gases
Ultrasonic clamp-onHigher accuracy; unaffected by pipe wall and coatingRequires pipe to be cut; ultrasonic is non-invasive
Coriolis mass flow meterMuch lower cost at large line sizes; negligible pressure dropVolumetric only, so density and mass must be inferred

Our guide to flow meter types and selection sets these technologies against fluid type, accuracy and installed cost across the full range.

Limitations to Plan Around

  • Conductive liquids only. No hydrocarbons, no gases, no steam, no ultrapure water.
  • Volumetric, not mass. Where mass flow is required and density varies, a Coriolis meter measures it directly.
  • Requires a full pipe. Partially filled gravity lines need a dedicated partially filled design.
  • Sensitive to earthing. Straightforward to get right at installation, tedious to diagnose afterwards.
  • Liner is a consumable in abrasive duty. Budget for periodic inspection where solids loading is high.

Magnetic Flow Meters from Dimens

Our electromagnetic flow meter range covers water, wastewater, chemical and slurry duty with a choice of liner and electrode materials matched to the process. Send us the fluid, its conductivity, the pipe size and the minimum, normal and maximum flow rates, and we will confirm the correct bore, liner and electrode combination before you order. Contact the Dimens measurement team for sizing support across Turkey, the European Union and export markets.

Frequently Asked Questions

How does a magmeter work?

Field coils generate a magnetic field across the pipe bore. As a conductive liquid flows through that field it induces a voltage across two electrodes in the pipe wall, in accordance with Faraday’s law. The voltage is directly proportional to flow velocity, and velocity multiplied by the known bore area gives volumetric flow.

What is the minimum conductivity for a magmeter?

Most instruments require about 5 microsiemens per centimetre, with some designs working down to 1 µS/cm. Tap water is typically 50 to 800 µS/cm and is comfortably measurable. Hydrocarbons, ultrapure water and gases cannot be measured by a magmeter at all.

How accurate is an electromagnetic flow meter?

Typically ±0.2 to ±0.5 percent of reading across the usable velocity range, with the better figures requiring individual wet calibration. Because the specification is a percentage of reading rather than of full scale, accuracy holds up well at low flow.

What is the difference between a magmeter and an electromagnetic flow meter?

There is none. They are two names for the same instrument. Electromagnetic flow meter is the formal term used in European specifications; magmeter is the shorter form common in water and wastewater practice.

How much straight pipe does a magmeter need?

Five pipe diameters upstream and two to three downstream as a working minimum. Allow more upstream where the meter follows a pump, a partially open control valve or two elbows in different planes.

Why is my magmeter reading unstable?

Inadequate earthing is the most common cause, particularly on plastic or lined pipework where earthing rings have been omitted. Other causes are a partially filled pipe, air entrained at the electrodes, insufficient straight run upstream, and an insulating coating built up on the electrode faces.

Can a magmeter measure a slurry?

Yes, and slurry service is one of its main applications. There is no obstruction to block and no moving part to wear. Specify an abrasion-resistant liner such as polyurethane or ceramic, and keep the velocity between 1 and 3 m/s to avoid both settling and accelerated wear.

Can a magmeter measure oil or fuel?

No. Hydrocarbons are effectively non-conductive and induce no measurable voltage. Use a Coriolis, turbine, positive displacement or ultrasonic meter instead.

In this article

Related products

All Flow Meters →

Written by

Engineering Support

Need the right product for your process?

Explore our comprehensive product range and discover how we can help you achieve precise and efficient measurements. Contact us today for a free consultation.